No O&M Manual for That Gear? Settle It on the Product Data Submittal

Name the gear with no manufacturer O&M manual on the product data transmittal, so the engineer agrees to the substitute data a year before the binder.

When a panelboard, transformer or surge protective device has no manufacturer O&M manual, say so on the product data submittal, name each item, and state what O&M data you'll furnish instead. The engineer answers it while they're already reviewing that gear. At closeout, the O&M transmittal points back to that answer, and nobody hunts through the binder for a manual that was never coming.

Here's how it usually goes. The product data gets approved in March. Nobody mentions O&M. In February of the next year the binder goes in, and it comes back with "Provide manufacturer's O&M manual for LP-2A, XFMR-T1, SPD-1." The engineer reviewing it may not be the one who stamped the product data. They've never heard that panelboards don't come with manuals, and from their chair, three items with nothing but a cut sheet look like three items you forgot.

You know what to put in their place. The trouble is when you're saying it: in a comment response, a year late, with retainage riding on the next review cycle.

Why the binder is the wrong place to explain it

A reviewer checks an O&M manual item by item against the equipment list. Any item without a manual reads as an omission, because nothing in the binder says otherwise. You end up explaining yourself in round two, and round two at closeout costs more than any other review cycle on the job.

The product data submittal is a better place for the conversation, for three reasons:

  • The reviewer is already looking at that gear. The catalog numbers, ratings and datasheets are on their desk. A note about its O&M data costs them one more line to read.
  • The answer lands on the record. Their response to the submittal is a dated, stamped document you can cite later. A phone call with the rep isn't.
  • A "no" comes back with time attached. If the engineer insists on something more, you learn it with a year to get it, not a week.

What the substitute O&M data should contain is covered in no O&M manual from the manufacturer? What to submit. This article is about getting the engineer to agree to it early.

Find the no-manual items while you build the submittal

You already pull every datasheet once, for the product data. Look for the manual in the same sitting, as getting the O&M manual when you get the datasheet describes. Most items turn one up. A few won't, and those are usually the same few on every job: panelboards, dry-type transformers, surge protective devices, terminal blocks, enclosures, sometimes a disconnect.

Call the rep on the ones that come up empty, and ask a narrow question: "Do you publish an O&M manual for this, or is the instruction bulletin it?" Write down what they say. The items they confirm go on your no-manual list. The ones still waiting on an answer go on it too, marked as pending.

Say it on the product data transmittal

Put the list in the notes of the product data transmittal. Name each item by tag, say what the manufacturer does publish, and say what the O&M manual will contain for it. Then ask the question outright, so a silent stamp can't be mistaken for an answer:

O&M DATA, ITEMS WITHOUT A MANUFACTURER O&M MANUAL

The manufacturers of the items below publish no separate O&M
manual. For each item, the O&M manual will contain the
installation instructions, the datasheet marked for the supplied
product, and a one-page O&M data sheet (operation, maintenance
tasks with their source, replaceable parts, service contact)
arranged per Section 01 78 23.

  LP-2A    Panelboard            Instruction bulletin
  XFMR-T1  Dry-type transformer  Installation instructions
  SPD-1    Surge protective dev. Installation and user guide

Please confirm this O&M data is acceptable for these items, or
note what else is required.

Keep it short and keep it on the transmittal, not buried in the product data. The transmittal is the page the reviewer reads first and the one the log keeps. What else that page has to carry is in what a transmittal has to say.

If the review comes back stamped with no word on your note, that isn't a yes. Ask once more in writing, at the next progress meeting so it lands in the minutes, or in an email to the reviewer. You're after one sentence you can quote later.

When the spec says "manufacturer's O&M manual" in so many words

Read the equipment paragraph of your Section 01 78 23 before you write the note. Many ask for "operation and maintenance data," which your substitute data answers directly. Some ask for the "manufacturer's printed O&M manual" for every item, and a sheet you wrote can't be the manufacturer's anything.

On those jobs the note on the transmittal may not be enough, because you're asking the engineer to accept something other than what the contract names. That's a question for an RFI, sent early and answered on the record. The deciding test is in submittal or RFI?, and what to look for in the spec section is in reading 01 78 23.

Point back to the answer on the O&M transmittal

At closeout, repeat the list on the O&M manual's transmittal, now with where each item's data lives and the answer you got:

Items without a manufacturer O&M manual: LP-2A, XFMR-T1, SPD-1.
O&M data furnished as stated on Submittal 40 61 13-002 Rev 0,
accepted by email 2026-04-06. See the Equipment chapter for each
tag: instructions, marked datasheet and O&M data sheet.

Now the reviewer opening the binder knows, before they turn a page, which items have no manual, why, and who already agreed to it. If the closeout reviewer is new to the job, you've handed them the history in four lines.

Write the sheet once and keep it with the part

The same panelboard shows up on your next job, and the one after that. Write its O&M data sheet once, file it with the part instead of the job folder, and the next project's no-manual list is a copy and paste. Update the sheet when the manufacturer revises the instructions, the same way you'd keep datasheets current.

How Submittal Kit handles this

Finding the no-manual items is the slow part, and it happens while you build the product data. On every submittal, the equipment list counts the parts still missing a manual and filters to them, even on an action submittal where manuals aren't required. The Parts Library's Missing manual filter lists every part across your company with none, and a part's Find documents panel can search the web for one. See Find datasheets.

The note goes in the Notes field of the submittal's Transmittal section, which prints in the transmittal's NOTES block on every compile. An O&M manual is a submittal too, so add a Transmittal section from the section palette and put the closeout note there. See Configure sections.

Upload the O&M data sheet you wrote as the part's Manual. It fills that item's Equipment chapter in every O&M manual that includes the part, on this job and the next one, and the Missing manual mark on the manual's equipment list goes away. See O&M manuals and Part documents.

Disclosure: I build Submittal Kit, and the note above works on any transmittal, whatever prints it.

Where this lives in Submittal Kit

Want to see your BOM become a reviewable package?

Bring a CSV or Excel BOM, or use a demo project. You'll see the proposed matches before anything changes and review the compiled PDF before issue.

Book a walkthrough